Outline SC40301 - the 12G/T630 - 12.5/16/20 outdoors high vacuum circuit breaker is the three phase ac outdoors high-voltage switch equipment, mainly uses in the 12KV rank, nominal current 630A, the nominal frequency 50HZ agricultural net, the city net, the mine, the railroad, the harbor electrical power distribution system, specially is suitable for the outdoors overhead line, the analysis and synthesis load current, the excess current, the short-circuit current, to electrical network perform handover and protection. This product is suitable for the below working condition: A. Ambient temperature -40 °C ~ +40 °C ; B. The elevation does not surpass 2000mm, above 2000mm and the user consultation; C. The wind pressure does not surpass 700Pa (to be equal to wind speed 34m/s); D. The relative humidity date mean value is not bigger than 95%, the monthly mean value is not bigger than 90% e. Air contamination degree III level; F. The surrounding air should not receive the caustic gas or the ignitable gas and so on the obvious pollution; G. Non- regular strenuous exercise; H. Should conform to the GB655386 related use situation requirement as the insulation medium silica gel. Main technical parameter 3.1 Fixed parameter Serial number | Project | Unit | Paramete | 1 | rated voltage | KV | 12 | 2 | nominal currents | A | 630 | 3 | Nominal frequency | HZ | 50 | 4 | Labor frequency durable voltage | KV | 42/48 | 5 | lightning surges voltage (peak value) | KV | 75/85 | 6 | The rating short-circuits the drop-out current | KA | 6.3 | 12.5 | 16 | 20 | 7 | The rating short-circuits the pass to gather the electric current (peak value) | KA | 16 | 31.5 | 40 | 50 | 8 | Fixed short-time durable electric current | KA | 6.3 | 12.5 | 16 | 20 | 9 | Fixed peak value durable electric current | KA | 16 | 31.5 | 40 | 50 | 10 | Fixed operation sequence | | 0.3S 180 | 11 | The rating short-circuit current opens breaks the number of times | sequence | 30 | 12 | Mechanical life | sequence | 10000 | 13 | Moves contact permission attrition accumulation thickness | mm | 3 | 4 | 14 | The fixed operation voltage matches the CT spring to hold the drive mechanism | Gathers floodgate coil | V | Direct current or exchange 220V | Minute floodgate coil | 15 | Has flowed the trip coil fixed operating current | A | 5 | 16 | Current transformer one, secondary current ratio | | 100/5.200/5.300/5.400/5.630/5 | 17 | Stored energy electrical machinery | The guest decides the voltage | V | Direct current or exchange 220V | Power | W | ≤ 200 | 18 | Weight | Kg | 150 |
3.2 Mechanical parameter Serial number | Project | Unit | Paramete | 1 | 1 contact starts is apart from | mm | 11±1 | 2 | contacts travelling schedules | mm | 3±0.5 | 3 | evenly to divide equally the floodgate speed | m/s | 1±0.2 | 4 | Average Gathers floodgate speed | m/s | 0.8±0.2 | 5 | Gathers floodgate bounces the time | ms | ≤3 | 6 | Three-phase minute floodgate same time | ms | ≤2 | 7 | Three-phase Gathers floodgate same time | ms | ≤3 | 8 | Gathers floodgate time | ms | 40-60 | 9 | Minute floodgate time | ms | 30-50 | 10 | Each extremely main return route resistance | ms | ≤200 | 11 | Alternates with the center distance | | 220±1.5 | 12 | Gathers floodgate condition contact spring length | mm | 25.5 |
3.3 Isolator engineering data Serial number | Project | Unit | Paramete | 1 | Rated voltage | KV | 12 | 2 | Nominal current | A | 630 | 3 | 4s thermally stable electric current (has effect value) | KA | 20 | 4 | Moves the steady state current (peak value) | KA | 50 | 5 | 1.2/50 mu s full wave striking potential (peak value) | KV | Relatively 75 Fracture 85 | 6 | 1min labor frequency pressure resistance | KV | 42 | 7 | Each electric conduction return route resistance | μΩ | ≤ 60 | 8 | Gathers floodgate manual operation moment of force | Nm | ≤ 150 | 9 | Touched the knife just to gather the position to incline | mm | ≤ 2 | 10 | The current carrying part insulates the distance to the place | mm | ≥ 160 | 11 | The fracture opens the distance | mm | ≥ 200 |
|
|
The contour and installs the size
Chart two SC40301 isolation knife external dimensions
1. Touches place 2. Touches knife 3. Supporting insulator 4. Tension bar insulator 5. The association sensitively installs 6. Circuit breaker 7. Isolates tool rest 8. Moves touches closes 9. Handle